When the "Cross Reference" function of a Step7 project file is not available, the following error message may appear: plan 1: The project is reorganized via the menu "File->Reorganize" as shown in Figure 2 below: Click "OK" as shown in Figure 3 below: The failed project files will be reorganized and have a reorganization success message prompt, as shown in Figure 4 below: Scenario 2: Check the box with "With reorganization (slow)". Note that this check will check all errors in the failed project and reorganize them, as shown in Figure 6 below: Set the project name and make a storage path. Clicking "OK" will check all errors of the failed project and restore its original internal structure. Metal Clad Sockets,Timer Plug Socket,2 Gang Socket,Silver Plug Sockets Guangdong Jinli Electrical Appliance Co., Ltd , https://www.sokelectric.com
- Unable to generate cross reference data
- Some components of Step7 cannot be opened
- Internal data structure failure/discontinuity can solve the above problems in two ways:
Open the failed project file in Step 7, as shown in Figure 1 below:
Figure 1: Opening a failed project file
Figure 2: Reorganizing a failed project
Figure 3: Confirmation of project reorganization
Figure 4: Reorganization success prompt box
Open the failed project file and save the project as a new project file via the menu "File->Save as..", as shown in Figure 5 below:
Figure 5: Save the failed project as a new project file
Figure 6: Tick option when saving a failed project as