1, open the software CX-Programmer 2, PLC - direct online - CP1L Ethernet online Click OK In the middle there will be a pop-up "OK box for uploading the program", click "OK" The interface after completion is as follows: 3, set After the connection is completed, some PLC information will appear on the left, double-click "Settings", as shown below 4, upload setting information from the PLC (options ---- transfer from the PLC) 5, Ethernet settings (move the tab to the right, click on the "built-in Ethernet" tab) You can configure IP, subnet mask, gateway here (Note: If you reconfigure the IP address, the FINS node number must be the same as the last digit of the IP address.) Configure a gateway at the IP routing table and configure DNS information at the DNS settings. 6, the gateway configuration Click on "Ins" The above IP address input: 0.0.0.0 (Adaptive) The following router IP address is entered, the address of the first switch from the PLC. 8, download to PLC After the setting is completed, download the set information to the PLC Option ----- Transfer to PLC Or pop up a check box to select to download the Ethernet configuration and port configuration to the PLC. 9, restart after power off After the configuration information is downloaded to the PLC, the PLC is powered off and restarted (power off time is preferably longer than 10 seconds). After the restart, the configuration information takes effect. After rebooting, you can reconnect the PLC to see if the configuration information is correct. Hifi Earbuds,Best Hifi Earbuds,Hifi In Ear Headphones,Best Hifi Earphones Dongguang Vowsound Electronics Co., Ltd. , https://www.vowsound.com